Washroom lights not operating Indicator: Water Supply & Fans operating normally but no lights Cause: External Light source affecting ambient light sensor | Solution: - Move light source
- Move sensor
- Adjust ambient light sensitivity as per Instruction Manual
|
No function from any output Indicator: No operation from any component Cause: No power | Solution: Ensure power supply is good and check all connections and Fuses. |
Indicator: No operation from any component Cause: Sensor mounted Incorrectly | Solution: - Position sensor where it will detect movement
- Ensure sensor is positioned away from door and other objects
- Position Sensor No higher than 2.4 Metres above the floor level
|
Lights and fans operate as normal but water supply does not turn off Indicator: Water still operates even though the lights and fans have timed out Cause: dv/dt is affecting the operation of the solenoid valves | Solution: Attach supplied snubbers to output terminals 5+6 /Cold 1+2 & 7+8/Hot 1+2 (if Fitted) |
All functions permanently on Indicator: All controlled functions still function after timed outputs have elapsed Cause: Key switch on | Solution: Turn key switch off and test |