+44 (0)118 969 1611

Washroom Control FAQs

Please click the question/ problem below to view the answer.

Washroom lights not operating
Indicator:
Water Supply & Fans operating normally but no lights

Cause:
External Light source affecting ambient light sensor
Solution:
  • Move light source
  • Move sensor
  • Adjust ambient light sensitivity as per Instruction Manual
No function from any output
Indicator:
No operation from any component

Cause:
No power
Solution:
Ensure power supply is good and check all connections and Fuses.
Indicator:
No operation from any component

Cause:
Sensor mounted Incorrectly
Solution:
  • Position sensor where it will detect movement
  • Ensure sensor is positioned away from door and other objects
  • Position Sensor No higher than 2.4 Metres above the floor level
Lights and fans operate as normal but water supply does not turn off
Indicator:
Water still operates even though the lights and fans have timed out

Cause:
dv/dt is affecting the operation of the solenoid valves
Solution:
Attach supplied snubbers to output terminals 5+6 /Cold 1+2 & 7+8/Hot 1+2 (if Fitted)
All functions permanently on
Indicator:
All controlled functions still function after timed outputs have elapsed

Cause:
Key switch on
Solution:
Turn key switch off and test